APC PDU

APC PDU

Plugin: go.d.plugin Module: snmp

Maintained by Netdata

Overview​

Monitor APC PDU (pdu) with Netdata over SNMP. Netdata recognizes the device automatically by its sysObjectID (recognized across 4 device identifiers) and collects the metrics this profile declares — on top of the generic SNMP baseline — with no manual OID configuration.

Netdata's SNMP collector matches the device to the apc-pdu.yaml profile via sysObjectID/sysDescr, then polls the OIDs it declares.

This integration is supported on all platforms.

This integration supports multiple instances configured side-by-side.

Default Behavior​

Auto-Detection​

Auto-detected as APC PDU via sysObjectID/sysDescr.

Limits​

The default configuration for this integration does not impose any limits.

Performance Impact​

The default configuration for this integration is not expected to impose a significant performance impact on the system.

Setup​

You can configure the snmp collector in two ways:

MethodBest forHow to
UIFast setup without editing filesGo to Nodes → Configure this node → Collectors → Jobs, search for snmp, then click + to add a job.
FileIf you prefer configuring via file, or need to automate deployments (e.g., with Ansible)Edit go.d/snmp.conf and add a job.
important

UI configuration requires paid Netdata Cloud plan.

Prerequisites​

SNMP access​

SNMP must be enabled on the device and reachable from the Netdata Agent acting as the site's SNMP hub.

Configuration​

Options​

Configure the SNMP collector with the device hostname and SNMP credentials. See the SNMP collector reference for all options.

via UI​

Configure the snmp collector from the Netdata web interface:

  1. Go to Nodes.
  2. Select the node where you want the snmp data-collection job to run and click the ⚙ (Configure this node). That node will run the data collection.
  3. The Collectors → Jobs view opens by default.
  4. In the Search box, type snmp (or scroll the list) to locate the snmp collector.
  5. Click the + next to the snmp collector to add a new job.
  6. Fill in the job fields, then click Test to verify the configuration and Submit to save.
    • Test runs the job with the provided settings and shows whether data can be collected.
    • If it fails, an error message appears with details (for example, connection refused, timeout, or command execution errors), so you can adjust and retest.

via File​

The configuration file name for this integration is go.d/snmp.conf.

The file format is YAML. Generally, the structure is:

update_every: 1
autodetection_retry: 0
jobs:
- name: some_name1
- name: some_name2

You can edit the configuration file using the edit-config script from the Netdata config directory.

cd /etc/netdata 2>/dev/null || cd /opt/netdata/etc/netdata
sudo ./edit-config go.d/snmp.conf
Examples​

There are no configuration examples.

Alerts​

There are no alerts configured by default for this integration.

Metrics​

On top of the generic SNMP baseline (the Generic SNMP Device integration — interfaces, system, IP/TCP/UDP, host resources), this APC PDU profile adds the metrics below. Each is collected only where the device exposes the matching OID — inclusion means the profile requests it; availability depends on the device model and software.

34 metrics in 9 groups; each row is a chart context usable in alerts.

GroupMetrics
Hardware / Bank1
Hardware / Outlet3
Hardware / Phase1
Hardware / PhaseBank2
Hardware / PowerSupply3
Hardware / Sensor5
Network / TCP12
Network / UDP6
System / Uptime1

Hardware / Bank​

Metric (chart context)UnitScopeDescription
snmp.device_prof_rPDUStatusBankState{status}per powernet_r_pdu_status_bank_index, powernet_r_pdu_status_bank_numberBank load state

Hardware / Outlet​

Metric (chart context)UnitScopeDescription
snmp.device_prof_rPDUOutletStatusLoadAper powernet_r_pdu_outlet_status_index, powernet_r_pdu_outlet_status_outlet_nameOutlet load for an Outlet Monitored Rack PDU
snmp.device_prof_rPDUOutletStatusOutletState{status}per powernet_r_pdu_outlet_status_index, powernet_r_pdu_outlet_status_outlet_nameOutlet state
snmp.device_prof_rPDUStatusOutletState{status}per powernet_r_pdu_status_outlet_index, powernet_r_pdu_status_outlet_numberOutlet Load state

Hardware / Phase​

Metric (chart context)UnitScopeDescription
snmp.device_prof_rPDUStatusPhaseState{status}per powernet_r_pdu_status_phase_index, powernet_r_pdu_status_phase_numberPhase Load state

Hardware / PhaseBank​

Metric (chart context)UnitScopeDescription
snmp.device_prof_rPDULoadStatusLoadAper powernet_r_pdu_load_status_indexPhase/bank load
snmp.device_prof_rPDULoadStatusLoadState{status}per powernet_r_pdu_load_status_indexPhase/bank load state

Hardware / PowerSupply​

Metric (chart context)UnitScopeDescription
snmp.device_prof_rPDUPowerSupply1Status{status}deviceStatus of power supply 1
snmp.device_prof_rPDUPowerSupply2Status{status}deviceStatus of power supply 2
snmp.device_prof_rPDUPowerSupplyAlarm{status}deviceAlarm status of the PDU power supply

Hardware / Sensor​

Metric (chart context)UnitScopeDescription
snmp.device_prof_rPDU2SensorTempHumidityStatusHumidityStatus{status}per powernet_r_pdu2_sensor_temp_humidity_status_name, powernet_r_pdu2_sensor_temp_humidity_status_typeCurrent state of the humidity probe
snmp.device_prof_rPDU2SensorTempHumidityStatusRelativeHumidity%per powernet_r_pdu2_sensor_temp_humidity_status_name, powernet_r_pdu2_sensor_temp_humidity_status_typeRelative humidity percentage
snmp.device_prof_rPDU2SensorTempHumidityStatusTempCCelper powernet_r_pdu2_sensor_temp_humidity_status_name, powernet_r_pdu2_sensor_temp_humidity_status_typeTemperature in degrees Celsius
snmp.device_prof_rPDU2SensorTempHumidityStatusTempFdegFper powernet_r_pdu2_sensor_temp_humidity_status_name, powernet_r_pdu2_sensor_temp_humidity_status_typeTemperature in degrees Fahrenheit
snmp.device_prof_rPDU2SensorTempHumidityStatusTempStatus{status}per powernet_r_pdu2_sensor_temp_humidity_status_name, powernet_r_pdu2_sensor_temp_humidity_status_typeCurrent state of the temperature probe

Network / TCP​

Metric (chart context)UnitScopeDescription
snmp.device_prof_tcpActiveOpens{transition}/sdeviceTCP connections transitioning from CLOSED to SYN-SENT
snmp.device_prof_tcpAttemptFails{failure}/sdeviceFailed TCP connection attempts
snmp.device_prof_tcpCurrEstab{connection}deviceCurrent TCP connections in ESTABLISHED or CLOSE-WAIT state
snmp.device_prof_tcpEstabResets{reset}/sdeviceTCP connections reset from ESTABLISHED/CLOSE-WAIT
snmp.device_prof_tcpHCInSegs{packet}/sdeviceTCP segments received
snmp.device_prof_tcpHCOutSegs{packet}/sdeviceTCP segments sent
snmp.device_prof_tcpInErrs{error}/sdeviceTCP segments received with errors
snmp.device_prof_tcpInSegs{packet}/sdeviceTCP segments received
snmp.device_prof_tcpOutRsts{reset}/sdeviceTCP segments sent with RST flag
snmp.device_prof_tcpOutSegs{packet}/sdeviceTCP segments sent
snmp.device_prof_tcpPassiveOpens{transition}/sdeviceTCP connections transitioning from LISTEN to SYN-RCVD
snmp.device_prof_tcpRetransSegs{retransmit}/sdeviceTCP segments retransmitted

Network / UDP​

Metric (chart context)UnitScopeDescription
snmp.device_prof_udpHCInDatagrams{packet}/sdeviceUDP datagrams received
snmp.device_prof_udpHCOutDatagrams{packet}/sdeviceUDP datagrams sent
snmp.device_prof_udpInDatagrams{packet}/sdeviceUDP datagrams received
snmp.device_prof_udpInErrors{error}/sdeviceUDP datagrams received but couldn't be delivered (not due to missing app)
snmp.device_prof_udpNoPorts{error}/sdeviceUDP datagrams received with no app on the destination port
snmp.device_prof_udpOutDatagrams{packet}/sdeviceUDP datagrams sent

System / Uptime​

Metric (chart context)UnitScopeDescription
snmp.device_prof_systemUptimesdeviceTime since the system was last rebooted or powered on.

Troubleshooting​

Other Problems​

Collect Diagnostics for Netdata Support​

For SNMP metrics, BGP, licensing, or topology issues, follow Collect SNMP troubleshooting data to include built-in diagnostics in a support bundle. SNMP evidence is unsanitized; share the bundle through a restricted Netdata Support ticket.


Do you have any feedback for this page? If so, you can open a new issue on our netdata/learn repository.